| Lab Option A | Lab Option B | Lab Option C | |
| Square Feet | 1,350 | 630 | 462 |
| Lab Bench top (see below for detail) | Approx (75) linear feet of open bench workspace (not including Fume Hoods) | Approx (42) linear feet of open bench workspace (not including Fume Hoods) | Approx (32) Linear feet of open bench workspace (not including Fume Hoods) |
| Lab Bench type (see below for detail) | A, B, C | C | A |
| # included cubicles | 6 | 4 | None |
| # of technical desks | 8 | 4 | 2 |
| Tech desk space/storage | Approx (32)-Linear feet of Tech desk with storage | Approx (16) Linear feet of Tech desk with storage | Approx (8) linear feet of Tech desk with storage |
| Tall storage | (21) Linear feet of lockable Tall Storage cabinets | (3) Linear feet lockable Tall Storage cabinets | None |
| Fume hoods | (4) Four 6’-0 Fume Hoods with (1) cup sink each, cold water and Lab Air services each hood | (2) Two 6’-0 Fume Hoods with (1) cup sink, cold water and Lab Air services | (2) Two 6’-0 Fume Hoods with (1) cup sink, cold water and Lab Air services |
| Sinks | (3) Three sink stations with HW/CW, hand eyewash and drying rack | (2) Two sink stations with HW/CW, hand eyewash and drying rack | (2) Two sink stations with HW/CW, hand eyewash and drying rack |
| Overhead service carrier | (6) Six linear feet of overhead service | (6) Six linear feet of overhead service | None |
| Equipment space | (8) Linear feet of open floor space for floor mounted equipment, (ie Refrigerators, Freezers, Incubators, centrifuge, Biological Safety Cabinets | None | (5) Linear feet of open floor space for floor mounted equipment, (ie Refrigerators, Freezers, Incubators, centrifuge, Biological Safety Cabinets |
| Emergency eyewash / shower unit | Wall unit and sink stations | Wall unit and sink stations | Sink stations |
1. Base cabinets are Conventional Steel.
2. Specialty cabinets include Acids and Corrosives, Flammable and Vacuum pump storage.
3. Tall Storage lockable cabinets 7’-0’’HT x 36’’W with adjustable shelving.
4. Work surfaces are 1’’ thick Epoxy for lab benches and plastic laminate for tech desks. Shelving will consist of wall and island adjustable units matching casework and work surfaces.
5. Sinks (28’’x15’’x12’’DP) Epoxy resin integrally molded to lab bench.
6. The Laboratory services include Hot water, Cold water, Natural Gas, Lab Grade Compressed Air at 15 psig.
7. Emergency Shower and Eyewash units (ES/EW) deluge type shower with pull on-push off control valve. Eyewash units are barrier free, wall mounted, and swing down eye/face wash units recessed in wall mounted stainless steel cabinet.
8. Overhead service carriers (include six foot movables tables below) with Lab Air and Natural Gas service.
9. Fume Hoods (Chemical) ventilated enclosure to capture and confine fumes, vapors and particulate produced or generated within the enclosure. Sash is a combination horizontal sliding and vertical rising unit.
Below details shared facility rooms available for tenants within The Accelerator. These facilities are available to tenants within The Accelerator, as defined by tenant’s lease, and will be managed and maintained by the Building Manager of The Accelerator.
Equipment Rooms - (4 available) total approx 200 square feet each room:
Approx (40) linear feet open floor space, with (1) floor drain.
Electrical outlets as follows:
(7) Standard 125V receptacles.
(4) 30 amp, 250V, Nema 6-30R
(2) Standard 125V receptacles on dedicated circuits.
Tissue Culture - (1) Total approx 220 square feet:
Approx (32) Linear feet open floor space.
Approx (6) linear feet of open bench top workspace (not including Fume Hoods).
(1) Sink station with HW/CW and deck mounted eyewash
(2) Standard cylinders gas storage.
Instrument Room - (1) Total approx 460 square feet:
Approx (6) linear feet open floor space.
Approx 50 linear feet of open bench top workspace (not including Fume Hoods).
(1) 4’-0’’ Chemical Fume Hood
(2) Sink stations with HW/CW and deck mounted eyewash
(4) Snorkel exhaust units that exhaust 100 CFM each.
(6) Standard cylinders gas storage.
Cold Room 4 degree C (1) Total approx 80 square feet:
Approx (20) linear feet Tall Storage Stainless steel metro-shelving.
Approx (3) linear feet of open bench top workspace.
(1) Sink stations with HW/CW.
Warm Room 37 degree C (1) Total approx 80 square feet:
Approx (28) linear feet Tall Storage Stainless steel metro-shelving.
Autoclave Suite 440 square feet:
Approx (12) linear feet open floor space.
Approx (24) linear feet of open bench top workspace.
(2) Sink stations with HW/CW and deck mounted eyewash
(1) Scullery Sink station 8’-0’L, with HW/CW, pre-rinse, & eyewash fixtures.
(1) Tall Flammable storage cabinet.
(3) Linear feet Tall Storage cabinets.
(1) Under counter glassware washer.
(1) Autoclave 24’’x36’’X48’’.
(1) Glass wash Oven.
Dark Room - (1) Total approx 190 square feet:
Approx (6) linear feet open floor space.
Approx 12 linear feet of open bench top workspace with base cabinet storage.
Sink station with HW/CW and deck mounted eyewash.
Cupsink with CW service.
(8) linear feet Tall Storage lockable cabinets.



Printable laboratory spec document